NO | Model | Input Type | OUT1~OUT4 Control Output | RS485communication | ||
TC | RTD | SSR | Transistor | |||
1 | GTAX_-S48 | * | * | * | ||
2 | GTAX_-T48 | * | * | * | ||
3 | GTAX_-S40 | * | * | |||
4 | GTAX_-T40 | * | * | |||
5 | GTAX_-S48-R | * | * | * | ||
6 | GTAX_-T48-R | * | * | * | ||
7 | GTAX_-S40-R | * | * | |||
8 | GTAX_-T40-R | * | * |
Sample rate | 1 times per second per channel |
Power supply | AC/DC 100 ~ 240V (85-265V) or AC/DC 24V |
Power consumption | < 6VA |
Environment | Temperature of indoor:0 ~ 50 no condensation, Humidity:<85%RH,altitude<2000m |
Storage environment | -10 ~ 60, no condensation |
SSR output | DC 24V pulse level, load<20mA |
Current output | DC 24 DC 100mA per channel |
Communication port | RS485 port, Modbus-RTU procotol |
Insulation impedance | Input, output, power cabinet>20MΩ |
ESD | IEC/EN61000-4-2 Contact ±4KV /Air ±8KV perf.Criteria B |
Pulse traip anti-interference | IEC/EN61000-4-4 ±2KV perf.CriGTEria B |
Surge immunity | IEC/EN61000-4-5 ±2KV perf.CriGTEria B |
Voltage drop & short interruption immunity | IEC/EN61000-4-29 0% ~ 70% perf.CriGTEria B |
Dielectric strength | Signal input & output & power 1500VAC 1min,below 60V Low voltage circuit between DC500V, 1min |
Total weight | About 400g |
Shell material | PA66-FR (Flame Class UL94V-0) |
Panel material | PVC film and PEM silicone key |
Power-off data protection | 10 years , times of writing: 1 million times |
Safety Standard | IEC61010-1 Overvoltage category ,pollution level 2, level (Enhanced insulation) |
Input Type | Measurement Range | Resolution | Accuracy | Input impedance/ Auxiliary current | Commincation Code | ||
TC | K | K1 | - 50~1200 | 1°C | 0.5%F.S±3digits | ||
K2 | -50.0~999.9 | 0.2°C | 0.5%F.S±1°C | ||||
J | J1 | 0~1200 | 1°C | 0.5%F.S±3digits | |||
J2 | 0.0~999.9 | 0.2°C | 0.5%F.S±1°C | ||||
E | E1 | 0~850 | 1°C | 0.5%F.S±3digits | |||
E2 | 0.0~850.0 | 0.3°C | 0.5%F.S±1°C | ||||
T | T1 | -50~400 | 1°C | 0.5%F.S±3°C | |||
T2 | -50.0~400.0 | 0.4°C | 0.5%F.S±3°C | ||||
B | 250~1800 | 1°C | 1%F.S±2°C | ||||
R | -10~1700 | 1°C | 1%F.S±2°C | ||||
S | -10~1600 | 1°C | 1%F.S±2°C | ||||
N | N1 | -50~1200 | 1°C | 0.5%F.S±1°C | |||
N2 | -50.0~999.9 | 0.2°C | 0.5%F.S±1°C | ||||
0~50mV | -1999~9999 | 12bit | 0.5%F.S±1°C | ||||
Note: RTD input is 2-wire type, and wire resistance compensation is not carried out. The length of
the sensor wire shall not exceed 5m, and the wire resistance shall not exceed 0.3Ω, otherwise the
measurement accuracy will be affected.