GTAX series four way temperature module


Quantity
Product description

Features:

  • Multiple thermocouple signal types for option, weak isolation between signal inputs,
  • able to connect grounding probe; Two wire RTD input.
  • With many functions, measured display, control output, alarm output, analog
  • output, RS485 communication, etc.
  • Optional many types of PID arithmetic, and with auto-tuning function.
  • Using for industrial machinery, machine tools,measuring instruments.
  • With limiting target value setting function

 

Model Illustration

 

General model description

NOModelInput TypeOUT1~OUT4 Control OutputRS485communication
TCRTDSSRTransistor
1GTAX_-S48

*

 

*

 

*

2GTAX_-T48

*

  

*

*

3GTAX_-S40

*

 

*

  
4GTAX_-T40

*

  

*

 
5GTAX_-S48-R 

*

*

 

*

6GTAX_-T48-R 

*

 

*

*

7GTAX_-S40-R 

*

*

  
8GTAX_-T40-R 

*

 

*

 

 

Specifications

Electrical parameters:

Sample rate1 times per second per channel
Power supplyAC/DC 100 ~ 240V (85-265V) or AC/DC 24V
Power consumption< 6VA
EnvironmentTemperature of indoor:0 ~ 50 no condensation,
Humidity:<85%RH,altitude<2000m
Storage environment-10 ~ 60, no condensation
SSR outputDC 24V pulse level, load<20mA
Current outputDC 24 DC 100mA per channel
Communication portRS485 port, Modbus-RTU procotol
Insulation impedanceInput, output, power cabinet>20MΩ
ESDIEC/EN61000-4-2 Contact ±4KV /Air ±8KV perf.Criteria B
Pulse traip anti-interferenceIEC/EN61000-4-4 ±2KV perf.CriGTEria B
Surge immunityIEC/EN61000-4-5 ±2KV perf.CriGTEria B
Voltage drop & short
interruption immunity
IEC/EN61000-4-29 0% ~ 70% perf.CriGTEria B
Dielectric strengthSignal input & output & power 1500VAC 1min,below 60V
Low voltage circuit between DC500V, 1min
Total weightAbout 400g
Shell materialPA66-FR (Flame Class UL94V-0)
Panel materialPVC film and PEM silicone key
Power-off data protection10 years , times of writing: 1 million times
Safety StandardIEC61010-1 Overvoltage category ,pollution level 2,
level (Enhanced insulation)

 

Measurement signal parameter

Input TypeMeasurement
Range
ResolutionAccuracyInput impedance/
Auxiliary
current
Commincation Code
TCKK1- 50~12001°C0.5%F.S±3digits

K2-50.0~999.90.2°C0.5%F.S±1°C

JJ10~12001°C0.5%F.S±3digits

J20.0~999.90.2°C0.5%F.S±1°C

EE10~8501°C0.5%F.S±3digits

E20.0~850.00.3°C0.5%F.S±1°C

TT1-50~4001°C0.5%F.S±3°C

T2-50.0~400.00.4°C0.5%F.S±3°C

B250~18001°C1%F.S±2°C
 
R-10~17001°C1%F.S±2°C  
S-10~16001°C1%F.S±2°C  
NN1-50~12001°C0.5%F.S±1°C  
N2-50.0~999.90.2°C0.5%F.S±1°C  
0~50mV-1999~999912bit0.5%F.S±1°C  
        

Note: RTD input is 2-wire type, and wire resistance compensation is not carried out. The length of
the sensor wire shall not exceed 5m, and the wire resistance shall not exceed 0.3Ω, otherwise the
measurement accuracy will be affected.

 

 

 

 

 