Characteristics
Specification
Product | Metal Tube Rotameter | |
Model | SUP-LZ | |
Range | Water (20) (01~200000) L/h Air (20,0.1013MPa) (0.03~3000) m³/h | |
Range ratio | Standard 10:1 Optional 20:1 | |
Accuracy | Standard: 1.5% Optional:1% Gas: 1.5% | |
Pressure | standard:DN15~DN504.0MPa DN80~DN2001.6MPa Optioanl: DN15~DN5032MPa DN80~DN20016MPa | |
Connection | Flange, Clamp, Thread, Sanity thread | |
Medium temperature | Standard: -20~120 PTFE 0~80 High temp: 120~450 low temp: -80~-20 | |
Environment temperature | Remote type: -40~85 Pointer type/local alarm type -40~100 | |
Power supply | Standard type: 24VDC two-wire system (4-20) mA (12VDC~32VDC) Alarm type: 24VDC multi-wire system (4-20) mA (12VDC~32VDC) AC type: (100~240) VAC 50Hz~60Hz Battery type: 3.6V@9AH lithium battery | |
Load resistance | RLmax: 600Ω | |
Alarm Output | Upper and lower limit instantaneous flow alarm Local alarm type: upper limit, lower limit or upper and lower limit instantaneous flow alarm (Contact capacity 1A@30VDC) Upper limit and lower limit alarm hold range is a maximum of 60% of range, and the minimum interval between upper and lower limit alarms is 10% of range | |
Pulse output | Cumulative pulse output is output of optocoupler signal isolation Darlington tube (internal 24VDC power supply, maximum current 8mA) | |
Ingress protection | IP65 |