No. | Model | Control output | Alarm |
1 | AI108-4/6/7/9-SB10-_ | SSR | 1 |
2 | AI108-4/6/7/9-SB10-_ | RELAY | 1 |
NOTE: T: TC input,including K/J/E/T; R: RTD input,including PT100/CU100/CU50
Sample rate | 2 times per second |
Relay capacity | AC 250V /3A life of rated load>100,00 times |
Power supply | AC/DC 100 ~ 240V (85-265V) |
Power consumption | < 6VA |
Environment | Temperature of indoor:0 ~ 50 no condersation; Humidity:<85%RH,altitude<2000m |
Storage environment | -10 ~ 60,no condersation |
SSR output | DC 24V pulse voltage,load<30mA |
Insulation impednce | input,output,power VS meter cover>20MΩ |
ESD | IEC/EN61000-4-2 Contact ±4KV /Air ±8KV perf.Criteria B |
Pulse traip anti-interference | IEC/EN61000-4-4 ±2KV perf.Criteria B |
Surge immunity | IEC/EN61000-4-5 ±2KV perf.Criteria B |
Voltage frop & Short interruption immunity | IEC/EN61000-4-29 0% ~ 70% perf.Criteria B |
Dielectric strength | Signal input & output & power 1500VAC 1min,below 60V low voltage DC500V,1min |
Total weight | About 400g |
Shell material | The shell and panel framePC/ABS (Flame class UL94V-0) |
panel material | PET(F150/F200) |
Power failure memory | 10years,times of writing:1 million times |
Panel protection level | IP65(IEC60529) |
Safety standard | IEC61010-1 overvoltage category,pollution level 2,level(Enhanced insulation) |
Specification of measuring signal table
Input | Measure range | Resolution | Accuracy | Input impedance/ Auxiliary current | |
TC | K | -50~400 | 1°C | 0.5% F.S ± 3 digits | > 500 ΚΩ |
J | 0~400 | 1°C | 0.5% F.S ± 3 digits | > 500 ΚΩ | |
E | 0~400 | 1°C | 0.5% F.S ± 3 digits | > 500 ΚΩ | |
T | -50~400 | 1°C | 0.5% F.S ± 2°C | > 500 ΚΩ | |
RTD | PT100 | -199~400 | 1°C | 0.5% F.S ± 3 digits | 0.2 mA |
CU50 | -50~150 | 1°C | 0.5% F.S ± 3°C | 0.2 mA | |
CU100 | -50~150 | 1°C | 0.5% F.S ± 1°C | 0.2 mA |